Page 85 - Kingspan Environmental Essential Guide

Basic HTML Version

Wastewater Solutions
84 85
SEPARATORS
A Range of Fuel/Oil Separators
Surface water drains normally discharge to a watercourse or indirectly into underground
waters (groundwater) via a soakaway. Contamination of surface water by oil, chemicals or
suspended solids can cause these discharges to have a serious impact on the receivingwater.
Where run-off is draining from relatively low risk areas such as car-parks and non-operational areas, a source control
approach, such as permeable surfaces or infiltration trenches, may offer a suitable means of treatment, removing the
need for a separator. Oil separators are installed on surface water drainage systems to protect receiving waters from
pollution by oil, which may be present due to minor leaks from vehicles and plant, from accidental spillage.
Effluent from industrial processes and vehicle washing should normally be discharged to the foul sewer
(subject to the approval of the sewerage undertaker) for further treatment at a municipal treatment works.
Full retention
Separators
Full retention separators treat the
full flow that can be delivered by the
drainage system, which is normally
equivalent to the flow generated by
a rainfall intensity of 65mm/hr.
On large sites, some short term
flooding may be an acceptable means
of limiting the flow rate and hence the
size of full retention systems.
ORDERING
CODE
Flow
(l/s)
Drainage
Area
(m
2
) PPG-3
(0.018)
Storage Capacity
(Ltrs)
Length
(mm)
Diameter
(mm)
Base Inlet
Invert
(
mm)
Base to
Outlet
Invert
(
mm)
Min.
Inlet Inlet
(
mm)
Standard
Pipework
Diameter
(
mm)
Silt
Oil
NSFP003
3
170
300
30
1700
1350
1420
1345
500
160
NSFP006
6
335
600
60
1700
1350
1420
1345
500
160
NSFA010
10
555
1000
100
2610
1225
1050
1000
500
200
NSFA015
15
835
1500
150
3910
1225
1050
1000
500
200
NSFA020
20
1115
2000
200
3200
2010
1810
1760
1000
315
NSFA030
30
1670
3,000
300
3915
2010
1810
1760
1000
315
NSFA040
40
2225
4000
400
4640
2010
1810
1760
1000
315
NSFA050
50
2780 5000
500
5425
2010
1810
1760
1000
315
NSFA065
65
3610
6500
650
6850
2010
1810
1760
1000
315
NSFA080
80
4445
8000
800
5744
2820 2500 2450
1000
300
NSFA100
100
5560 10000 1000
6200 2820 2500 2450
1000
400
NSFA125
125
6945 12500 1250
7365
2820 2500 2450
1000
450
NSFA150
150
8335 15000 1500
8675
2820
2550
2450
1000
525
NSFA175
175
9725
17500 1750
9975
2820
2550
2450
1000
525
NSFA200
200
11110 20000 2000 11280 2820
2550
2450
1000
600
 Rotomoulded chamber construction   
 GRP chamber construction
FEATURES
Fitted inlet / outlet
connections.
Vent points within necks.
Maintenance from
ground level.
Oil alarm probe tube
optional extra.
GRP or PE on model
construction dependent.
Certified to EN 858-12
and PPG3
Designed for easy
installation.
FREE